BJX Explosion Proof Junction Box

Applications:

Explosive gas atmosphere Zone 1 and Zone 2

Combustible dust areas Zone 21 and Zone 22

Explosive gas mixture classification IIA, IIB, IIC

Explosive gas ignition temperature group T1-T6

Technician specifications

Ex rating: Exe II T6 Gb, Exd IIB T6 Gb, Exd IIC T6 Gb, Ex tD A21 IP66 T80℃
Rated current: Up to 1000A

Rated voltage: 220/380/690V

IP grade: IP65, IP66

Corrosion-proof class: WF1, WF2

Materials: Aluminum alloy or stainless steel.

Thread for entry cable gland: G1/2"- G3"; NPT1/2 - NPT4; M20x1.5 - M115x1.5

Executive standard: GB3836.1, GB3836.2, GB3836.3, GB12476.1, GB12476.5;

IEC60079-0, IEC60079-1, IEC60079-7, IEC61241-0, IEC61241-1;

EN60079-0, EN60079-1, EN60079-7, EN61241-1

*Customized upon request. 


image.pngBJX Explosion Proof Junction BoxBJX Explosion Proof Junction Box

BJX Explosion Proof Junction BoxBJX Explosion Proof Junction Boximage.png